No . | Item | Unit | Specification | ||||||
1 | Rated Voltage | Kv | 2 × 27.5 | 27.5 | |||||
2 |
Rated
Insulation Level |
Kv | Between Phase | Phase To Earth | Isolation Across | Isolation Across | |||
1min Power Frequency Withstand Voltage | 180 | 122 | 95 | 95 | |||||
L ighting Impulse Withstand Voltage (Peak) | 420 | 260 | 200 | 200 | |||||
3 | Rated Frequency | Hz | 50 | 50 | |||||
4 | Rated Current | A | 1250, 1600, 2000, 2500 |
1250
,
1600
2000 , 2500 |
|||||
5 | Rated Short - Circuit Breaking Current (Effective Value) | kA | 25, 31.5 | 25, 31.5 | |||||
6 | DC Component Of R ated Short - Circuit Breaking Current (Percentage) | ≤42% | ≤42% | ||||||
7 | Rated Short-Circuit Making Current (Peak) | kA | 63, 80 | 63,80 | |||||
8 | Rated Peak Withstand Current | kA | 80 | 80 | |||||
9 | Rated Short-Time Withstand Current | 31.5 | 31.5 | ||||||
10 | Duration Of Rated Short-Circuit Current | s | 4 | 4 | |||||
11 | Rated Short-Circuit Breaking Current Breaking Times | times | 30 | 30 | |||||
12 | Braking Time | ms | ≤50 | ≤50 | |||||
13 | Arcing Time | ≤15 | ≤15 | ||||||
14 | Mechanical Life | times | 20000 | 20000 | |||||
15 | Rated Operating Sequence | O-0.3s -CO-180s-CO | O-0.3s -CO-180s-CO | ||||||
16 | M agnitude Of Partial Discharge (Applied Voltage 52.6kv, Measuring Voltage 44.6kv) | pC | < 10 | ||||||
17 | Degree Of Protection | IP45 | IP45 |