AC-3 Le1-D Gmw Magnetic Starter for Overload Protection

Model NO.
gmw
Theory
Thermal Relay
Electricity Type.
AC
Usage
to Start and Control Motor
Transport Package
Standard Export Package
Specification
CE
Trademark
KASAN, ORIGINAL, AOLKW, OEM
Origin
Zhejiang China (Mainland)
Production Capacity
10000PCS/Month
Reference Price
$ 4.50 - 9.00

Product Description

LE1-D old type

LE1-D magnetic starter is mainly applied to circuit of AC 50 or 60Hz, voltage up to 550V for far distance making and breaking circuit and frequently starting and controlling motor. It has the features of small volume, light weight, safe and reliable performance etc.

General Description:

LE1-D series magnetic motor starter are suitable for 50Hz or 60Hz, rated voltage up to 660V, current up to 95A circuit. In order to protect motor starting, accelerating the motor to rated rev, against overload operation and artificially breaking the circuit of protected motor.

Structure Feature:

1. Sealed: Plastic box LE1-D09~D32 and iron box platstic coated LE1-D40~D95, protection up to IP65;

2. Operation system with manual "START" and "STOP" buttons. With thermal overload relay consisting a inversable starter;

3. Install different accessories derive many kinds of other products;

4. Select LC1-D contactor with standard 35mm rail, which can be fixed directly at the base of starter. Wires extracted from the three phase of the thermal overload relay can be inserted the three phase main contacts of the contactor, easy assembly and connection.
Maximum power AC3 duty (kW) Rated current (A) Matched thermal relay (A)
220V 380V 660V
230V 400V 690V
2.2 4 5.5 9 LR2 D13
3 5.5 7.5 12 LR2 D13
4 7.5 10 18 LR2 D13
5.5 11 15 25 LR2 D13
7.5 15 18.5 32 LR2 D23
11 18.5 30 40 LR2 D33
15 22 33 50 LR2 D33
18.5 30 37 65 LR2 D33
22 37 45 80 LR2 D33
25 45 45 95 LR2 D33

 

 